Hunter X-CORE Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 32
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
10
PSR Series
Pump Start Relay
15 ft Minimum (4.5 m)
To Pump
ST AR T TIMES
SEASONAL ADJUSTMENT
WATER DAYS
ALL
MANUAL-ALL STATIONS
START TIMES
SYSTEM OFF
CURRENT TIME/DAY
RUN TIMES
ACTIVE
SENSOR BYPASS
RUN
NOTE: Complete this section only if you have a
pump start relay installed. A pump start relay is
a device that uses a signal from the controller to
actuate a separate electrical circuit to energize a
pump to provide water to your system.
The controller should be mounted at least a 15 ft (4.5 m) away from
both the pump start relay and pump to minimize any potential
electrical interference.
1. Route a pair of wires from the pump relay into the controller.
2. Connect a common wire to the C (Common) terminal inside the
controller and connect the remaining wire from the pump start
relay to the P (Pump) terminal.
Relay holding current draw must not exceed 0.3 A. Do not connect
the controller directly to the pump or damage to the controller will
result.
CONNECTING A PUMP START RELAY
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 31 32

Comentarios a estos manuales

Sin comentarios